Products

Three-Phase Harmonic Filters

It is used in series with capacitor groups in compensation systems. By using these devices, the capacitor impedance can be increased against the harmonic currents generated on the system, the resonance frequency can be shifted and kept below the frequencies generated by the main harmonic currents.

ENTES triphase harmonic filter reactors are high-quality reactors designed to protect the compensation system by suppressing harmonics in reactive power control systems.

TECHNICAL SPECIFICATIONS

Power (kVAr):0.83

L(mH): 46,14

Irms(A):1.36

Ith(A): 1.50

IIIn(A):2,43

C*(uF):5.44

Operating Voltage: 400V 50Hz

Resonance Frequency: 189 Hz

P-Factor: 7%

Weight (kg): 1.5

Qty/Parcel: 1